Outdoor-air economizers and enthalpy changeover during a power outage
Economizer enthalpy changeover uses outdoor temperature and humidity to decide whether outdoor air can help cool your building (PNNL). During a power outage, an outdoor-air damper with a spring return to the closed position shuts when its actuator loses power (PNNL). An air-side economizer lets the HVAC system cool with outside air when outdoor conditions are favorable (PNNL).
An automatic transfer switch calls for the standby generator to start when utility power fails and transfers the load back to the grid when it returns (PNNL Standby).
What the changeover compares
An economizer can use either dry-bulb temperature, which is the air temperature, or enthalpy, which accounts for temperature and moisture (PNNL). With fixed enthalpy control, outdoor air qualifies for economizer cooling when its enthalpy is lower than a preset limit (PNNL Controls). With differential enthalpy control, the comparison is against the enthalpy of the air coming back from inside the building (PNNL Controls). A basic dry-bulb control looks for outdoor temperature to fall within its allowed range (PNNL). A controller with a return-air temperature sensor may instead use outdoor air for cooling when it is cooler than the return air (PNNL). The control also needs a call for cooling before it starts economizing (PNNL). In PNNL’s air-handler simulator, high and low outdoor-temperature lockouts can be added even when the economizer uses a strategy other than fixed dry-bulb control (PNNL Controls). In that setup, the high lockout disables economizing above its outdoor-temperature setpoint, and the low lockout disables it below its setpoint (PNNL Controls).
What the dampers do during normal operation
The outdoor damper meters fresh air into the unit, and the return damper regulates how much indoor air the system recirculates (PNNL). When outdoor air can help cool the building, the controller opens the outdoor damper while closing the return damper, using actuators that move together (PNNL). Most systems also have a relief or exhaust damper to let air out and keep pressure from building up as more outdoor air comes in (PNNL). The controller may use a sensor in the mixed or supply air to adjust the damper position and reach the target air temperature (PNNL). During operating hours, the outdoor damper usually stays slightly open for ventilation even when conditions are not favorable for economizing (PNNL).
What to verify on standby power
The economizer relies on air-handling equipment such as ductwork, relief or exhaust dampers and fans to work correctly (PNNL). Its outdoor-air contribution can reduce the amount of mechanical cooling needed in favorable weather, and the equipment may still use compressor cooling to help meet the load (PNNL). An overloaded generator can overheat and pose a fire hazard (OSHA). Qualified personnel can test a diesel standby system by initiating transfer and running it under the full building load while recording generator voltage, coolant temperature and oil pressure, following the manufacturer's maintenance recommendations (PNNL Standby). For home standby sizing, Generac says a motor can draw more power at startup than it does once it is running (Generac). Generac says a professional home site survey measures both demands and checks the electrical panel before equipment is ordered (Generac).
Humidity sensors and maintenance
A controller can calculate enthalpy from temperature and humidity readings taken in the same airstream (PNNL). A drifted humidity reading can introduce enough error to make the economizer operate incorrectly, so humidity sensors used for enthalpy control need regular calibration (PNNL). If staff lack the resources for routine calibration, a dry-bulb limit may improve how the economizer operates (PNNL). Have a qualified technician confirm the intended control sequence, check the sensors and verify that the dampers move through the expected positions (PNNL). Where the building automation system records trends, the technician can review outdoor and return-air readings alongside the damper positions (PNNL).
Generator safety during an outage
A qualified electrician must install a transfer switch before any generator is connected directly to the building wiring (OSHA). Without that isolation, generator power can travel onto utility lines and electrocute lineworkers or others nearby (OSHA). Never run a generator indoors or in any enclosed space, including a garage or basement (OSHA). Leaving windows and doors open may still allow carbon monoxide to accumulate (OSHA). Outdoor placement must also be clear of doors, windows and vents that could draw in exhaust (OSHA). Carbon monoxide from generator exhaust is poisonous and has no color or smell (OSHA).
Frequently asked
What happens to the damper when the whole unit shuts down?
For shutdown, the outdoor-air damper should be closed, and some actuators use a mechanical spring to return it to that position when power drops (PNNL). While the HVAC is running with economizing disabled, the normal occupied damper position is usually slightly open to admit ventilation air (PNNL).
Does every rooftop unit use the same damper arrangement?
Packaged rooftop units typically link the outdoor and return dampers so one actuator moves both (PNNL). A built-up air handler generally uses a separate actuator for each of the two dampers (PNNL).
What if the outside air feels cool but humid?
An enthalpy control takes moisture into account alongside temperature when it evaluates outdoor air (PNNL). A basic dry-bulb limit makes its decision using the outdoor temperature range (PNNL). Humidity may be weighed along with dry-bulb temperature when deciding whether outdoor conditions favor economizing (PNNL).
Why is my thermostat flashing “Cool On” after an outage?
On some residential systems, a thermostat can delay the compressor restart after a power loss to protect the equipment (Trane). A flashing “Cool On” message or a “Wait” display can indicate that delay, depending on the thermostat (Trane).
Do I need to call a pro for this?
Yes. The work belongs to a licensed contractor. Economizer diagnostics and maintenance involve electrical and mechanical hazards and require experienced personnel (PNNL). A qualified electrician must handle the transfer switch for a generator connected to the building (OSHA).
Related
- Adding air conditioning to a commercial generator
- Thermostat setpoints for a commercial building on emergency power
- Server room and data room cooling on generator power
- Commercial Heat Pumps: Types, Where They Fit, What to Check
- Chiller System: How It Works and Whether It Fits a Building
- Heat Pumps in Florida, and What Salt Air Does to the Outdoor Unit
Need a generator supplied? Blume can supply a generator; the electrical installation is referred to a licensed electrician. Blume Mechanical Service, license CAC-1822618, serves Pinellas, Hillsborough and Pasco counties.
Sources: PNNL, Air-side economizer operation and maintenance, https://www.pnnl.gov/projects/om-best-practices/air-side-economizers · PNNL Controls, Building Re-Tuning Simulator, air handler configuration, https://retuning-simulator.pnnl.gov/module/define-ahu/action/1 · PNNL Standby, Standby generator operation and maintenance, https://www.pnnl.gov/projects/om-best-practices/standby-generators · OSHA, Hurricane eMatrix, generator use, https://www.osha.gov/etools/hurricane/activity-sheets/building/removal-floodwater · Generac, Home standby generator sizing, https://www.generac.com/resources/home-management/what-size-generator-do-i-need/ · Trane, Thermostat startup delay, https://www.trane.com/residential/en/resources/troubleshooting/thermostat-controls/thermostat-blinking-cool-on/