HVAC, explained
Server room and data room cooling on generator power
Backup power for data center cooling can help keep the equipment from overheating during an outage (Schneider Electric). When cooling is backed up by generator power only, it shuts down briefly until the facility transfers to the generator, and it may then take several minutes to restart and return to full cooling (Schneider Electric).
Tampa Electric counted nearly 600,000 outages after Hurricane Milton, mostly from uprooted trees and debris that brought down overhead lines and poles (Tampa Electric). Schneider Electric says servers can keep running on an uninterruptible power supply, or UPS, while their cooling is down, and overheating can still take the servers offline (Schneider Electric).
How long will the racks go without cooling?
Schneider Electric says a UPS typically carries critical equipment through the gap before the generator takes over, and the generator supplies power for the longer outage (Schneider Electric). In a data center with generator-only cooling, that gap includes both the time before the electrical transfer and the time the cooling equipment needs to come back up to full output (Schneider Electric). Schneider Electric says a data center averaging no more than 5 kW per rack may have several minutes before IT equipment overheats if the room has plenty of space for cool air, as it might with high ceilings (Schneider Electric). Racks with much higher power density can overheat within seconds, and Schneider Electric says UPS backup for some or all of the cooling system can make sense in that setting (Schneider Electric).
Size for motor startup and the loads already running
Rehlko says a motor starting at full voltage typically draws six times its rated full-load current (Rehlko). The current remains elevated as the motor accelerates to roughly 75 percent of its rated speed (Rehlko). Rehlko says a motor can pull generator voltage down enough during startup to keep the motor from getting up to speed (Rehlko). A deep drop can also cause control relays or motor starter contactors to release, and the motor may fail to start (Rehlko). Rehlko says sizing should account for motor startup and limit the effects of voltage or frequency dips on other connected equipment (Rehlko). A UPS is one example of a voltage-sensitive load that needs to be considered in that same sizing decision (Rehlko). The motor nameplate provides information for determining the starting load in kilovolt-amperes, or kVA (Rehlko).
What a starter or drive changes
Rehlko says a solid-state starter raises motor voltage gradually and can have an adjustable starting-current limit (Rehlko). Changing the settings in the field changes the performance predicted at the original settings (Rehlko). Rehlko also says the starter can distort voltage during startup (Rehlko). With a variable-frequency drive, Rehlko identifies distortion of the voltage waveform as the concern to evaluate and recommends checking whether the generator sizing software can predict voltage harmonics for nonlinear loads (Rehlko).
Measure the air reaching the servers
ENERGY STAR reports that the 2008 ASHRAE recommendation was 64.4 to 80.6 degrees Fahrenheit for air entering the front of the server (ENERGY STAR). Cooling controls can respond to the air at the servers instead of relying on the temperature of air returning to the cooling unit, and the equipment’s safe operating range matters when setting those controls (ENERGY STAR). When feasible, experienced operators typically monitor at the front near the bottom of each rack, at the front near the top and at the upper rear, which is usually the hottest part (ENERGY STAR). Those front readings show how cool the arriving air is and whether it reaches the top of the rack (ENERGY STAR). Blanking panels fill empty spaces in a rack so supply air goes through the equipment, which can lower the temperature at the server inlets (ENERGY STAR). Where several cooling units serve the same room, centralized controls can coordinate their airflow using inlet and return temperatures (ENERGY STAR). The controls can also coordinate humidity management across units, avoiding a situation where one unit adds moisture while another removes it (ENERGY STAR).
Keep portable generators outdoors
Generac warns that carbon monoxide in generator exhaust can kill within minutes (Generac). Generac says to always run a portable generator outside of the home (Generac). Always run it outdoors, far from windows, doors, vents and other openings where exhaust can enter (Generac). For a portable generator serving a home, Generac warns never to feed power into the wiring through a wall outlet (Generac). That can send electricity back onto utility lines and seriously injure or kill the workers restoring power (Generac). For a connection to household wiring, a qualified electrician should install a transfer switch (Generac).
Frequently asked
Does the server UPS keep the air conditioner running?
Schneider Electric says many data centers put IT equipment on UPS power and back up cooling with the generator alone (Schneider Electric). Schneider Electric says a cooling system may need a UPS that is independent of the one used for IT equipment (Schneider Electric).
How can a chilled-water system cover the restart gap?
Schneider Electric identifies stored cooling as one way to cover the time a chiller needs to restart (Schneider Electric). It also recommends providing reserve cooling capacity and choosing equipment that can return to service sooner (Schneider Electric).
What can warn staff that racks are heating up?
Rack sensors can alert staff when temperatures are likely to move beyond safe operating conditions (ENERGY STAR). Data center managers can use that information to adjust cooling, airflow or the IT load (ENERGY STAR).
Can a generator with enough running capacity still struggle at startup?
Yes. Rehlko says a motor starting on generator power can draw enough current to depress voltage and slow or prevent acceleration to operating speed (Rehlko).
Do I need to call a pro for this?
Yes. The work belongs to a licensed contractor. For a portable generator connected to household wiring, Generac says a qualified electrician should install the transfer switch (Generac).
Related
- Adding air conditioning to a commercial generator
- Thermostat setpoints for a commercial building on emergency power
- Outdoor-air economizers and enthalpy changeover during a power outage
- Running an AC on a home generator: load management
- Chiller System: How It Works and Whether It Fits a Building
- Commercial Heat Pumps: Types, Where They Fit, What to Check
- Generator carbon monoxide and backfeeding: safe placement and wiring
Blume Mechanical Service, license CAC-1822618, serves Pinellas, Hillsborough and Pasco counties.
Sources: Schneider Electric, Cooling continuity during a power failure, https://blog.se.com/education-research/2014/09/25/ensure-data-center-cooling-system-can-ride-power-failure/ · Schneider Electric, UPS design for data centers, https://blog.se.com/datacenter/2020/07/20/design-considerations-deployment-ups-systems-in-data-centers/ · Rehlko, Generator sizing for motor starting, https://techcomm.rehlko.com/$web/techcomm/contentful/G26-7_Sizing%20Generators%20for%20Motor%20Starting_WP.pdf · ENERGY STAR, Data center temperature guidance, https://www.energystar.gov/products/data_center_equipment/5-simple-ways-avoid-energy-waste-your-data-center/raise-temperature · ENERGY STAR, Sensors and controls for data centers, https://www.energystar.gov/products/data_center_equipment/16-more-ways-cut-energy-waste-data-center/use-sensors-and-controls · ENERGY STAR, Data center airflow management, https://www.energystar.gov/products/data_center_equipment/16-more-ways-cut-energy-waste-data-center/manage-airflow-cooling-efficiency · Generac, Portable generator safety, https://www.generac.com/portable-power-solutions/portable-generator-safety/ · Tampa Electric, Hurricane Milton restoration update, https://www.tampaelectric.com/mediacenter/2024/Tampa-Electric-Achieving-Power-Restoration-Milestones-After-Hurricane-Milton/