Air conditioner starting current and generator size
On the single-phase 1.5- to 5-ton R-410A scroll compressors covered by Copeland bulletin AE4-1331, startup normally draws at least six times rated running current for 100 to 300 milliseconds (Copeland). In Generac's sizing method, if the air conditioner has the largest extra starting load, that load is added to the total running watts (Generac). Once a household has identified its essential power needs for an outage, Utah Emergency Management recommends having a licensed electrician determine the appropriate kind and size of generator (Utah Emergency Management).
For a Tampa Bay homeowner planning for an outage, keeping the air conditioner on is both a running-power and a starting-power question. Generac calls the continuous demand running watts and uses additional starting watts for the brief extra demand when a motor comes on (Generac).
Size for the moment the compressor starts
Generac's sizing method adds the running watts of the equipment that will be on together, then adds the largest extra starting load in that group (Generac). Rehlko also accounts for how far voltage falls when a motor starts and what that dip does to equipment sharing the supply (Rehlko).
What locked rotor amps tell you
Copeland says that on the single-phase versions of its 1.5- to 5-ton R-410A scroll compressors covered by bulletin AE4-1331, inrush is normally at least six times rated running current (Copeland). The surge typically lasts 100 to 300 milliseconds, ending as the rotor begins to move (Copeland). Copeland determines the nameplate locked rotor amps, or LRA, by holding the rotor stationary, applying the highest voltage on the label and taking the current reading after four seconds (Copeland). Copeland says inrush current and locked rotor amps are one and the same (Copeland). Copeland says a weak supply may sag under high inrush, and that lower starting voltage cuts the compressor's starting torque and keeps the rotor stationary longer (Copeland).
Starting figures for specific heat pumps
Carrier rates the single-phase, 208-to-230-volt 25SCA5 size 24 compressor at 59.5 locked rotor amps and 11.1 rated load amps (Carrier). The size 36 compressor is rated at 83.1 locked rotor amps and 15.3 rated load amps, while size 60 is rated at 150.0 locked rotor amps and 25.6 rated load amps (Carrier). Daikin specifies 4.4 and 4.9 starting amps for the RXS09LVJU and RXS12LVJU outdoor units, respectively, paired with the matching FTXS indoor units at 208 to 230 volts and 60 Hz (Daikin). With the corresponding FDXS indoor units, Daikin lists 4.6 and 6.4 starting amps for those same outdoor models (Daikin).
Read the conditions on the generator rating
Rehlko says the acceptable voltage dip depends on what the motor and the other equipment on the system can tolerate (Rehlko). Too much sag can knock control relays offline or keep the motor from starting (Rehlko). For single-phase 240-volt, 60-Hz configurations at a voltage dip of just over a third, Kohler gives peak motor-starting ratings of 33 kVA for the 14RCA, 41 kVA for the 20RCA and 39 kVA for the 26RCA (Kohler). Kohler labels these figures peak motor starting kVA (Kohler).
Soft starters and hard-start kits
Eltwin shows a 3-ton example with inrush falling from 109 amps to 33 amps with its SureStart soft starter (Eltwin). Its 5-ton example goes from 158 to 47 amps, and its 7-ton example goes from 185 to 56 amps (Eltwin). Eltwin says the reduction in peak demand can allow a smaller generator with SureStart (Eltwin). Supco's SPP6 is a hard-start kit that combines a PTC relay with a start capacitor and is intended to increase starting torque (Supco). Eltwin characterizes hard-start kits as shortening the start while leaving the initial current demand in place (Eltwin).
Portable generator safety during an outage
Never run a portable generator inside the house or in the garage, even with the garage door open (Utah Emergency Management). Gasoline generator exhaust contains carbon monoxide, a poisonous gas with no visible color or detectable smell (Utah Emergency Management). Outdoor operation requires at least 20 feet of clearance from vents, windows and doors (Utah Emergency Management). Never feed power from a generator into a household receptacle or straight into the main electrical panel (Utah Emergency Management). Electricity can travel back onto utility lines and shock or kill workers restoring service (Utah Emergency Management). A licensed electrician must install a transfer switch for a generator that will power the home's wiring (Utah Emergency Management).
Frequently asked
Is a 14 kW generator enough for a 5-ton air conditioner?
Kohler says its 14 kW 14RCA can easily handle startup and operation of a 5-ton air conditioner (Kohler). For actual appliance demand, Kohler points to the appliance maker's specifications and recommends consulting a Kohler Power Systems professional to size the generator for the home (Kohler).
How does an inverter mini-split behave when the room reaches temperature?
Trane says a conventional system may switch off at the set temperature and start again minutes later, using more energy at each outdoor-unit start than during regular operation (Trane). Trane says Mitsubishi inverter mini-splits avoid that cycling pattern by varying output and can run longer at lower capacity (Trane).
Does lower starting voltage make a compressor easier to start?
No. Copeland says lower line voltage lowers locked rotor amperage in proportion on the scroll compressors covered by its bulletin (Copeland). On the single-phase models, lower starting voltage also reduces starting torque and lengthens the time the compressor stays in a locked rotor condition (Copeland).
Do I need to call a pro for this?
Yes. The work belongs to a licensed contractor. A licensed electrician can size the generator around the loads you need and must install the transfer switch if the generator will feed the house wiring (Utah Emergency Management).
Related
- Running an AC on a home generator: load management
- What a 20 kW home standby generator can run
- What a 24 to 26 kW home standby generator can run
- How many watts an air conditioner uses, and how to work it out from the label
- Restarting an air conditioner after a power outage
- Generator carbon monoxide and backfeeding: safe placement and wiring
- What a 10 kW home standby generator can run
Need a generator supplied? Blume can supply a generator; the electrical installation is referred to a licensed electrician. Blume Mechanical Service, license CAC-1822618, serves Pinellas, Hillsborough and Pasco counties.
Sources: Generac, https://www.generac.com/globalassets/residential/home-standby-generators/buyers-guide/hsb_buyersguide_brochure_2024_v6.pdf · Rehlko, https://techcomm.rehlko.com/$web/techcomm/contentful/G26-7_Sizing%20Generators%20for%20Motor%20Starting_WP.pdf · Copeland, https://apps.copeland.com/Publications/AEB/AE4_1331_R9.pdf · Carrier, https://www.shareddocs.com/hvac/docs/1009/Public/08/25SCA5-01PD.pdf · Daikin, https://daikincomfort.com/docs/default-source/lv-series-wall-mount/sm-fd(t)xs09-36lvju-rk(x)s09-36lvju.pdf · Kohler, https://resources.kohler.com/power/kohler/residential/pdf/g4270.pdf · Kohler, https://resources.kohler.com/power/kohler/residential/pdf/g4272.pdf · Kohler, https://resources.kohler.com/power/kohler/residential/pdf/g4315.pdf · Eltwin, https://www.eltwin.com/download/18.27db44e31727359e8b74c61/1594307551301/SureStart-Single-Phase-Specification-Catalog.pdf · Supco, https://supco.com/web/supco_live/products/SPP6.html · Trane, https://www.trane.com/residential/en/resources/troubleshooting/ductless-systems/do-mini-splits-turn-off-when-temperature-is-reached/ · Utah Emergency Management, https://dem.utah.gov/generator-safety/