HVAC, explained
What a 20 kW home standby generator can run
The Generac 20 kW models G007038-1 and G007039-1 are rated for a maximum continuous 20,000 watts on propane and 18,000 watts on natural gas, at 240 volts (Generac sheet). The Generac owner's manual, which covers units from 10 to 26 kilowatts, describes these generators as suitable for typical residential loads such as sump pumps, refrigerators, air conditioners, furnaces, computers, lighting and microwaves, when sized correctly (Generac manual).
The same 20 kW unit gives a different rating on each fuel. Generac lists 20,000 watts on propane and 18,000 on natural gas for its 20 kW model (Generac sheet). Kohler's single-phase 20RCA (120/240 volts) is rated 20 kilowatts on propane and 18 kilowatts on natural gas (Kohler sheet). Both makers' ratings fall as altitude and heat rise (Generac sheet; Kohler sheet).
Ratings by model and fuel
Generac's 20 kW model draws 83.3 amps on propane and 75.0 amps on natural gas at 240 volts, behind a 90 amp main line circuit breaker (Generac sheet). The owner's manual gives the same 83.3 amp figure on propane and a 90 amp breaker for that model (Generac manual). Kohler's 20RCA, single-phase at 120/240 volts, is rated 18 kilowatts and 75 amps on natural gas, and 20 kilowatts and 84 amps on propane, behind a 100 amp line breaker (Kohler sheet). The Kohler sheet's three-phase rows, 20RCAL and the 2G7 version of the 20RCA, are listed at 17/21 kW/kVA on both fuels (Kohler sheet). Cummins's RS20A and RS20AC list 75 amps on natural gas and 83.3 amps on propane vapor (Cummins sheet).
Derating for altitude and heat
Generac says its maximum falls about 3.5 percent for each 1,000 feet above sea level, and about 1 percent for each 10 degrees Fahrenheit above 60 degrees (Generac sheet, read November 2026). Kohler's guidelines are 4 percent for each 1,000 feet above 500 feet of elevation, and 2 percent for each 10 degrees Fahrenheit above 60 degrees (Kohler sheet, read November 2026). Cummins gives full rated power up to 60 degrees Fahrenheit at 0 feet, then a derate of 3.5 percent for each 1,000 feet and 1 percent for each 10 degrees Fahrenheit after that (Cummins sheet, read November 2026). The rated maximum also depends on fuel energy content and engine condition (Generac sheet).
What the standby rating allows
Generac's standby rating covers backup power for the length of a utility outage, when the unit is correctly maintained, and it carries no overload capability (Generac sheet). Kohler's standby rating assumes an average load of 80 percent over the outage, read November 2026, and specifies no overload capacity at that rating (Kohler sheet). Cummins's standby rating is likewise given for the duration of a normal power interruption and has no sustained overload capability (Cummins sheet).
Starting motors and air conditioners
The Cummins sheet for the Quiet Connect series, which includes the RS20A and RS20AC, says these units can start and run a 5-ton air conditioner under full pre-load (Cummins sheet). The same sheet notes that air conditioners vary by type and operating conditions, and advises consulting a qualified Cummins distributor for sizing (Cummins sheet). Cummins gives motor starting of 40 kVA for the RS20A and RS20AC at a 30 percent voltage dip, read November 2026 (Cummins sheet). Kohler's 2F7 single-phase 20RCA has a peak motor starting figure of 41 kVA at 240 volts and 60 Hz, at a 35 percent voltage dip, read November 2026 (Kohler sheet). Kohler advises confirming each appliance's actual power need with its manufacturer (Kohler sheet).
Overload and load management
In the manual's troubleshooting table, an overload alarm is described as the unit shutting down during operation; the listed steps are to check the LEDs or screen for alarms, clear the alarm, take household loads off the generator, then put it in AUTO and restart (Generac manual). The Generac manual lists Smart Management Modules (50 and 100 amps) as an accessory that manages large loads at startup and sheds them when the generator is overloaded (Generac manual).
Fuel use at full and half load
Generac's 20 kW model burns 204 cubic feet per hour of natural gas at half load and 301 at full load, which is 5.78 and 8.52 cubic meters per hour (Generac sheet). On propane it burns 87 cubic feet per hour (2.37 gallons per hour) at half load and 130 cubic feet per hour (3.56 gallons per hour) at full load (Generac sheet). Kohler's 20RCA burns 8.0 cubic meters per hour (281 cubic feet) of natural gas at full load and 4.6 cubic meters (161 cubic feet) at half load (Kohler sheet). On propane the same unit burns 3.9 cubic meters per hour (136 cubic feet) at full load and 2.3 cubic meters (82 cubic feet) at half load (Kohler sheet). Cummins's RS20A and RS20AC burn 268 cubic feet per hour of natural gas at full load and 112 cubic feet per hour of propane vapor (Cummins sheet).
Propane Btu figures
Generac's sheet says to multiply propane flow in cubic feet per hour by 2,500 to get Btu per hour (Generac sheet). The Propane Education and Research Council's table lists 350,000 Btu per hour at full load and 189,000 at half load for a 20 kilowatt generator (PERC guide). The table's notes say Btu needs may differ from one manufacturer or model to another, and that the chart is based on information provided courtesy of Generac (PERC guide).
Natural gas supply in a storm
Florida's emergency management office recommends keeping gas service on. Natural gas service is likely to keep running through the storm (Florida DEM). After a catastrophic storm, Peoples Gas may need to shut off some homes' gas at the meter for safety, and a customer whose gas is off will need to phone the Customer Care Center before service returns (Peoples Gas). The EIA says the average U.S. electricity customer had approximately five and one-half hours without power in 2022, a year with fewer major events than 2021 (EIA).
Safety requirements from the manuals
Only a licensed electrician should do the wiring and connections on this unit, and if installation requirements are not followed, death or serious injury and property damage could result (Generac manual). Never connect the unit to a building's electrical system unless an approved transfer switch has been put in by a licensed electrician, or death or serious injury will result (Generac manual). Use only approved switchgear to isolate the generator from the normal power source, or death, serious injury and equipment damage will result (Generac manual). Position the unit to prevent combustible material from accumulating underneath (Generac manual). A qualified professional technician or contractor has to make the fuel-line connection (Generac manual). The PERC guide says propane installations should be done by trained propane professionals (PERC guide). The Kohler 20RCA is designed for outdoor installation only (Kohler sheet). Generac's sheet lists an 18 inch minimum distance from a structure, under a listing that requires the unit to sit clear of doors, windows and fresh-air intakes, and to follow local codes (Generac sheet). Kohler's 20RCA meets NFPA guidelines for 18 inches of clearance to combustible materials, and says to check state and local codes for the minimum distance from a structure (Kohler sheet). The unit must be placed so that air can move freely into and out of it, and outdoor air intakes for air distribution systems must be at least 10 feet horizontally from the enclosure (Generac manual). The manual says to remove shrubs and tall grass within 3 feet of the louvers on the enclosure's sides, to site the unit on high ground clear of rising water, and not to run it in standing water (Generac manual). Running engines produce carbon monoxide, which will result in death or serious injury if not avoided (Generac manual). Keep a battery-operated carbon monoxide alarm running indoors at all times, installed as the manufacturer's instructions direct (Generac manual). Do not operate the unit indoors; fuel and vapors are extremely flammable (Generac manual). Only extinguishers that are fully charged and rated ABC by the NFPA are acceptable; a discharged or wrongly rated one will not put out electrical fires in automatic standby generators (Generac manual). Before working on the unit, disconnect utility power and render the unit inoperable, or death or serious injury will result (Generac manual). Do not manually transfer under load: disconnect the transfer switch from all power sources first, or death, serious injury and equipment damage will result (Generac manual). A rotten-egg or sulfur-like smell can mean damage to a gas line or a gas leak. Florida's emergency management office says to move to safety right away, call 911, and after that call your gas company's emergency line (Florida DEM). Peoples Gas puts moving to safety at 300 feet, about the length of a football field (Peoples Gas). Only qualified gas company representatives or emergency personnel should turn the main meter valve on or off (Florida DEM). If flood water has submerged gas appliances, do not try to operate them (Florida DEM).
Frequently asked
Does fuel type change the rating?
Yes. Generac's 20 kW model is rated 20,000 watts on propane and 18,000 watts on natural gas (Generac sheet). Kohler's single-phase 20RCA (120/240 volts) is rated 20 kilowatts on propane and 18 kilowatts on natural gas (Kohler sheet).
Can natural gas service be cut during a storm?
After a catastrophic storm, Peoples Gas may need to shut off some homes' gas at the meter (Peoples Gas). A customer whose service is off will need to call the Customer Care Center to have it restored (Peoples Gas).
What happens if a Generac 10 to 26 kW unit is overloaded?
In the manual's troubleshooting table, an overload alarm is described as the unit shutting down during operation; the listed steps are to check the LEDs or screen for alarms, clear the alarm, take household loads off the generator, then put it in AUTO and restart (Generac manual).
Do I need to call a pro for this?
Yes. The Generac owner's manual, which covers units from 10 to 26 kilowatts, says a qualified professional technician or contractor has to make the fuel-line connection (Generac manual). Wiring and connections on those units should be done by a licensed electrician only, since missing installation requirements could cause death, serious injury or property damage (Generac manual). A licensed contractor should handle the gas and electrical work.
Related
- Generator fuel for a long outage: propane, gas, diesel
- Generator carbon monoxide and backfeeding: safe placement and wiring
- Running an AC on a home generator: load management
Need a generator supplied? Blume can supply a generator; the electrical installation is referred to a licensed electrician. Blume Mechanical Service, license CAC-1822618, serves Pinellas, Hillsborough and Pasco counties.
Sources: Generac, Guardian Series 16/20/22 kW Residential Standby Generators spec sheet, https://www.generac.com/globalassets/products/residential/standby-generators/spec-sheets/16-22kw-guardian-standby-generator-specsheet.pdf · Generac, 18 kW Guardian Series Home Generator 7226 product page, https://www.generac.com/residential-products/standby-generators/gaseous/18kw-standby-generator-wifi-enabled-7226/ · Generac, Owner's Manual 60 Hz Air-Cooled Generators 10 kW to 26 kW, https://www.generac.com/globalassets/products/residential/standby-generators/owners-manual/g-10-26kw-60hz-standby-generator-owners-manual-en.pdf · Generac, Natural Gas Generators: No On-Site Fuel Storage, https://www.generac.com/industrial/tools-resources/project-planning/fuel-selection/natural-gas/performance/eliminate-bulky-fuel-storage/ · Kohler, G4-272 20RCA/20RCAL Generator Specification Sheet, https://resources.kohler.com/power/kohler/residential/pdf/g4272.pdf · Cummins, Quiet Connect Series RS13A, RS17A, RS20A and RS20AC specification sheet, https://mart.cummins.com/imagelibrary/data/assetfiles/0058055.pdf · Propane Education and Research Council, The Propane Technical Pocket Guide, https://cloudinary.propane.com/image/upload/v1664396780/Residential:Commercial/Brochures/4482-BR-21_Technical-Pocket-Guide_v3_HRpg.pdf · Florida Division of Emergency Management, Gas Utilities, https://www.floridadisaster.org/planprepare/home/gas-utilities/ · Peoples Gas, Peoples Gas is Prepared for Milton, https://www.peoplesgas.com/mediacenter/2024/peoples-gas-is-prepared-for-milton/ · U.S. Energy Information Administration, Today in Energy: electricity customers averaged five and one-half hours of power interruptions in 2022, https://www.eia.gov/todayinenergy/detail.php?id=61303