What is an economizer in HVAC? How it cools with outdoor air

An air-side economizer is a set of ducts and dampers, run by a controller, that lets an HVAC system bring in outdoor air to help meet the cooling load when the weather suits it (PNNL). It supplements compressor-based cooling with free cooling from fresh air whenever bringing that air in takes less energy than treating the return air (PNNL). Reaching the potential savings requires correct operation and adequate maintenance (PNNL).

Facility managers and building owners who look after air-handling equipment need to know how an economizer works, what its parts do, and where it can fail.

What an air-side economizer is

In a commercial HVAC system, the economizer counts as part of the air-handling equipment and depends on ductwork, relief or exhaust dampers, and fans to work correctly (PNNL).

Compared with compressor-based cooling, the economizer adds free cooling from fresh air when delivering that air takes less energy than conditioning return air (PNNL).

For PNNL's guide, an air-side economizer is dampers with their actuators and sensors, plus a controller that reads sensor data to set the damper position (PNNL). Exact layouts vary, since packaged rooftop units, built-up air handlers, equipment size and building type all change the components (PNNL).

The dampers that do the work

Two dampers do the core work, one for outdoor air and one for return air. Between them, they help meet the building's cooling load while outside conditions are suitable (PNNL).

The return-air damper sets how much air comes back from the conditioned spaces and gets recycled through the building again (PNNL).

When outside conditions suit economizing, the outdoor-air damper opens as the return-air damper closes, so both dampers need actuators that receive the same signal or synchronized signals (PNNL).

Packaged rooftop units typically have an accessory that links the two dampers to a single actuator, while built-up air handlers typically run two separate actuators (PNNL).

Most systems also include a relief or exhaust damper that works in parallel with the outdoor-air damper. It keeps the building from over-pressurizing and lets more outdoor air mix with the return air (PNNL).

The outdoor-air damper usually sits slightly open during operating hours, even when outside air is not suitable for economizing, so the building keeps its minimum ventilation (PNNL).

If the outdoor-air minimum is set too high, heating and cooling energy spent conditioning that outside air can climb even while the economizer is inactive (PNNL).

Why a fixed outdoor-air damper is less efficient

Without an economizer, commercial buildings typically rely on a fixed outdoor-air damper that admits a fraction of the total ventilation air volume in order to maintain indoor air quality (PNNL).

That fixed setting is kept as low as the calculated ventilation requirement permits, which limits the outdoor air that has to be treated in warm, hot or cold weather (PNNL).

As a result, even in mild weather, when outdoor air would need little cooling, the air reaching the cooling coil mostly comes from inside the building (PNNL).

A properly functioning economizer can vary the outdoor air it sends to the cooling coil, from the minimum ventilation level up to 100 percent (PNNL, read November 2026).

The economizer makes that shift when bringing in outside air costs less energy than conditioning return air (PNNL).

How the controls decide

Economizers can be run by enthalpy, a value calculated from temperature and humidity together, or by dry-bulb temperature (PNNL).

Controllers may use one of several strategies, and the chosen strategy determines which sensors are needed (PNNL).

The simplest limit control relies on an outdoor dry-bulb temperature sensor. The controller turns economizing on while outdoor temperature sits within an allowable range (PNNL).

With a return-air temperature sensor in place, the controller may switch economizing on if outdoor temperature reads lower than the return air (PNNL).

A mixed-air or supply-air temperature sensor can help the controller move the outdoor-air damper toward a desired temperature (PNNL).

Humidity sensors can be added on the outdoor and return air streams alongside the dry-bulb sensor, and their readings combine into an enthalpy value (PNNL).

A controller may be integrated, meaning the control algorithm is programmed into the HVAC controllers, or non-integrated, meaning a dedicated hardware module holds the algorithm (PNNL).

Humidity sensors used for enthalpy require regular calibration, and if that calibration lapses, large errors can cause the economizer to operate improperly (PNNL). Where calibration resources are unavailable, switching to a dry-bulb temperature strategy may improve operation (PNNL).

Recent building codes have called for a basic level of fault detection with dedicated and central economizer controls, which can speed review and alert staff to sensor or damper problems (PNNL).

Confirm the control method with the installer or operator before changing other settings.

What goes wrong when it is set up badly

A poorly controlled economizer may bring in more outdoor air than conditions justify (PNNL).

Extra outdoor air can raise energy use in both hot and cold weather, and hydronic systems may face a freezing risk when outdoor air drops below 32 °F (PNNL).

Whichever control method is used, the potential savings require correct setup and sustained maintenance (PNNL).

Without proper upkeep, an economizer can lead to poor indoor air quality, wasted energy and added costs, and such problems may go unnoticed or undiagnosed for an extended period (PNNL).

A run-to-failure approach is not suitable for economizers, so preventive maintenance has to be done on a regular schedule (PNNL).

Excessive vibration, rust, mold, fan failure, and clogged screens or filters can all affect how an economizer operates (PNNL).

The economizer depends on the proper function of other components, such as ductwork, exhaust or relief dampers, and fans (PNNL).

PNNL says that "operation, maintenance, and diagnostics of air-side economizers require knowledgeable and experienced personnel." Only trained and certified personnel should attempt the actions recommended in PNNL's guidance. If such personnel are not on hand, the actions should not be initiated (PNNL). Usual safety practices for electrical and mechanical work apply to these systems, and maintenance personnel face the electrical and mechanical dangers that mechanical systems powered by high-voltage electricity carry, as well as environmental hazards tied to where the equipment sits, such as accessing rooftops, mechanical rooms and basements (PNNL).

A sample checklist asks staff to inspect exterior openings and outdoor-air intakes for blockages, to check actuators, dampers, seals, linkages and gears, and to calibrate, repair or replace sensors as needed (PNNL). The checklist does not stand in for manufacturer recommendations or contracted O&M services, and trained, authorized staff should carry out all maintenance (PNNL).

Staff should confirm that dampers close fully with no air leakage, confirm that outdoor-air dampers are closed when the system is not running, and confirm that they are modulating open in appropriate conditions, meaning outdoor temperature falls between 45 and 65 °F while cooling is requested (PNNL). During heating-season warm-up, outdoor-air dampers should also remain closed (PNNL).

Trending data from the building automation system (BAS) is the most common way to check performance (PNNL). The most important data points include humidity and temperature of the outside and return air, the temperature of the mixed or supply air, the position of each damper, and zone CO2 where it is available (PNNL).

Recording maintenance in a logbook or a computerized maintenance management system helps show what was done and when (PNNL).

Cost and payback

In most climates, installing air-side economizers in new and existing buildings is easily recovered through energy savings (PNNL).

Cost-effectiveness has led air-side economizers to become widespread across the country (PNNL).

In 2013, Marvell Semiconductor's headquarters data center in Santa Clara, California, paid for its economizer in 2 years without a utility rebate and in 1.5 years with one (ENERGY STAR).

Ask a licensed contractor for a written estimate before you decide on any equipment change.

A written estimate should show the cost of the work and the basis for any savings figure.

Florida and hot climates

ENERGY STAR's data center guidance cites northern Florida as a place where an air-side economizer can be used about half of the year (ENERGY STAR).

Data centers need cooling every day of the year, so ENERGY STAR says air-side economizers may be worth considering in hot climates, where cooler evening and winter air can be used (ENERGY STAR).

Humidity control can cut into the savings an economizer delivers. In certain locations, air can be cool but very dry, and a lot of energy may then be needed to humidify it (ENERGY STAR).

Data center examples

In a data center, an economizer draws cool outside air in and sends it to the servers, while the server exhaust is directed outside (ENERGY STAR).

If the outside air is particularly cold, the economizer may blend warm exhaust air into the intake so that temperature and humidity stay within safe operating ranges for the equipment (ENERGY STAR).

Air-side and water-side economizers both cool a data center without running an air conditioner or a mechanical chiller (ENERGY STAR).

Data center operators may call this use of economizers free cooling (ENERGY STAR).

Integrated air-side economizers can provide additional savings compared with non-integrated packages (ENERGY STAR).

An integrated unit takes in fresh air once outside temperature falls below the return air temperature, instead of waiting until it reaches the server intake set-point (ENERGY STAR).

That lowers compressor load, because the cooler outside air is cooled instead of the warmer return air (ENERGY STAR).

Adding economizers to an existing data center may take work and money (ENERGY STAR). Oracle did not find a retrofit economical, because there was no easy route for the large volumes of outdoor air a raised-floor, downflow design needed (ENERGY STAR). Humidity and other contaminants were also concerns in that case (ENERGY STAR).

Intel ran a 10-month study from August 2008 in which outside air alone cooled a data center, across a temperature range of 64°F to 92°F, and saw no rise in server failures (ENERGY STAR). Humidity swung widely at times during that test (ENERGY STAR).

A 2016 study said that data center operators should stay mindful of humidity when air-side economizers are running (ENERGY STAR). Researchers collected data from nine Microsoft sites worldwide, and those sites hosted over 1 million disk drives (ENERGY STAR). Six of those sites were in hot, humid areas, and three were in cool, dry areas (ENERGY STAR).

The dry sites had the lowest failure rates no matter which cooling technology they used (ENERGY STAR). Internal relative humidity appeared to affect disk lifetime more than average temperature did, though temperature still had a significant effect (ENERGY STAR).

PG&E and Lawrence Berkeley National Laboratory found higher particle levels in data centers that used economizers than in those that brought in little outside air (ENERGY STAR). An improved filter design may ease contamination concerns (ENERGY STAR).

Economizers, whether air-side or water-side, can supply some cooling if mechanical cooling goes offline, which may lower the risk of data center downtime (ENERGY STAR).

ENERGY STAR contrasts an earlier data center average of 2-4 kW per rack with high-density computing, where the draw can reach 60 kW per rack (ENERGY STAR). One Intel facility used free cooling with up to 43 kW per rack, and with inlet air for servers at 95 degrees Fahrenheit, free cooling was feasible in all but 39 hours of the year (ENERGY STAR).

Frequently asked

What does an economizer do?

An air-side economizer uses outdoor air to help meet the cooling load when outside conditions are suitable (PNNL). It reduces the mechanical cooling the system must supply (PNNL).

Does an economizer use outdoor air all the time?

No. A properly functioning economizer can supply outdoor air from the minimum ventilation level up to 100 percent (PNNL, read November 2026), depending on conditions.

Can an economizer waste energy?

Yes, if it is controlled incorrectly. It may bring in more outdoor air than conditions justify (PNNL). Correct setup and maintenance are needed to reach the savings (PNNL).

Is an economizer worth the cost?

In most climates, the installation cost of an air-side economizer is recovered easily through energy savings (PNNL). Ask a licensed contractor for a cost estimate for your building.

Do I need a contractor for this?

Maybe, depending on the work. Reaching the potential savings requires correct operation and adequate maintenance (PNNL). A poorly controlled economizer may bring in more outdoor air than conditions justify (PNNL). For controls work, such as sensor calibration or controller setup, use a licensed contractor.

Related

Need an HVAC check on your commercial or home equipment? Blume Mechanical Service (CAC-1822618) repairs, installs and maintains HVAC and refrigeration equipment in Pinellas, Hillsborough and Pasco counties. Call 727-330-9131.

Last updated: 2026-11-21

Sources: Pacific Northwest National Laboratory — Best Practices for Air-Side Economizers Operation and Maintenance (https://www.pnnl.gov/projects/best-practices/air-side-economizers) · ENERGY STAR (U.S. EPA and DOE) — Use Air-Side Economizer (https://www.energystar.gov/products/data_center_equipment/16-more-ways-cut-energy-waste-data-center/use-air-side-economizer)