HVAC, explained

What a hydronic air handler is and how it differs from a refrigerant coil unit

First Co describes a hydronic fan coil as one where the water is the medium that moves heating or cooling energy to the coil (First Co fan coil page). A refrigerant-based fan coil instead has a cooling coil that belongs to a refrigeration circuit linked to other equipment, so the fan coil name alone does not show that a unit uses chilled water (First Co fan coil page).

First Co's FWA-HW manual is its installation manual for FWA-HW Series fan coil units (FWA-HW manual).

What a fan coil unit does

First Co says a fan coil unit pushes air over a coil that transfers heat, warming or cooling the space (First Co fan coil page). Its main parts are a fan with its motor, one or more coils, an enclosure, and controls (First Co fan coil page). Cooling versions also need a drain route for condensate (First Co fan coil page).

Hydronic: water as the energy carrier

First Co says that in hot-water heating, heated water runs through the coil and gives its heat to the air (First Co fan coil page). First Co says a hydronic unit relies on the connected plant for water at a suitable temperature and flow (First Co fan coil page). Other configurations use electric heat, or act as the indoor part of a heat-pump system (First Co fan coil page). Heating options vary by model, and fitting the opening is no proof of a match with the existing heat source (First Co fan coil page).

Refrigerant-based units

In a refrigerant-based unit, the cooling coil belongs to a refrigeration circuit that links to other equipment (First Co fan coil page). Such a unit needs a match to approved equipment and the right refrigerant configuration (First Co fan coil page). The fan coil name alone does not show that a unit uses chilled water (First Co fan coil page). First Co's chilled-water fan coil range covers hydronic equipment, and its multi-occupant ceiling fan coils cover refrigerant-based designs (First Co fan coil page).

Why the names overlap

First Co says the terms overlap; both air handlers and fan coils move and condition air (First Co fan coil page). Makers and project teams may use either name, depending on product family and application (First Co fan coil page). The UC Series is called a "wall-mount or closet air handler" in the wall-mount fan-coil category, and the HX Series is a horizontal recessed ceiling fan coil (First Co fan coil page).

Ceiling, wall-mount and vertical layouts

Ceiling units can leave occupied floor space free of equipment (First Co fan coil page). The HX Series is a horizontal recessed unit with cased and uncased options (First Co fan coil page). For ceilings, the page says to check depth, supports, duct connections, drain route and access for service once the ceiling is closed (First Co fan coil page). Wall-mount fan coils suit layouts planned around a vertical indoor unit (First Co fan coil page). A model's fit in an apartment's mechanical space depends on where its return air enters, door access and connection clearances (First Co fan coil page). The page says not to take equal nominal capacity as proof of matching electrical service, piping or cabinet dimensions (First Co fan coil page). The RR Series is in the vertical high-rise category, with chilled-water cooling and heating options that vary by model (First Co fan coil page).

Two-pipe and four-pipe piping

Two-pipe and four-pipe describe hydronic piping arrangements (First Co fan coil page). First Co says a typical two-pipe unit has a single supply and a single return for its water circuit (First Co fan coil page). First Co says a four-pipe unit has separate heating and cooling water circuits, so zones can call for either without a building-wide seasonal changeover when the plant and controls support it (First Co fan coil page). First Co's HYB Series includes both layouts, and the model choice has to fit the intended piping and control sequence (First Co fan coil page).

Hot-water coil limits and connections

The manual states "These instructions give information for installation of FWA-HW fan coil units only" (FWA-HW manual). The manual says not to exceed 400 psig (27.6 bar) of pressure in the water coil, or 180° F (82° C) of water temperature in the coil (FWA-HW manual). Connections are copper, sized 3/4 inch nominal with 7/8 inch OD, and flow through the coil is capped at 4.5 GPM (FWA-HW manual). An expansion tank may be required when a back-flow preventer is fitted to the system (FWA-HW manual).

Scalding and mixing valves

The manual calls hot water from a water heater "a serious safety hazard due to potential scalding" (FWA-HW manual). If the coil ties into domestic potable water, a mixing valve can be used to temper the water drawn for household use (FWA-HW manual). An anti-scald valve can be fitted in the hot water piping, which lets domestic water run cooler than the space heating water (FWA-HW manual).

Purging air and the first heat call

The manual says these systems are not built to hold air under pressure, and that they should only be tested with water (FWA-HW manual). The manual says the fan coil "should not be energized for heating until the hot water coil and all the water lines have been purged of air" (FWA-HW manual). For typical tank-type Aqua Therm piping, the water lines to and from the coil must come off the horizontal connection of the T fittings at the water heater, which clears air from the system whenever water is drawn in the dwelling (FWA-HW manual).

Electrical work, grounding and moving parts

Before servicing, turn off all power to the unit, which may have more than one disconnect (FWA-HW manual). Units with ECM motors have line voltage applied at all times, so the manual says to make sure power is disconnected before servicing (FWA-HW manual). The manual directs grounding of the fan coil, with the ground wire on the terminal marked with the protective earth symbol, and warns that failure to do so "can result in injury or death" (FWA-HW manual). The manual says "Do not touch any rotating component with any object" (FWA-HW manual).

Filter, fan, motor and coil care

The manual says the unit "must never run under any circumstances without an air filter in place" (FWA-HW manual). The manual says the unit must not be operated during construction, given excessive airborne dust and debris (FWA-HW manual). The manual says the filter should get cleaning or a replacement every 30 days, more often under severe conditions, and that a replacement should always match the type originally furnished (FWA-HW manual). Dust and other contaminants on the heat transfer surfaces interfere with airflow and impair heat transfer, so the coil must be kept clean (FWA-HW manual).

Warranty and parts

The manual says that altering the product or using non-authorized factory parts voids the warranty, and may create a hazardous condition for service personnel and occupants (FWA-HW manual). It adds that company employees and contractors cannot waive this warning (FWA-HW manual).

Frequently asked

Is a fan coil unit the same as an air conditioner?

Not necessarily. A fan coil can be the indoor cooling part of a system, but that is a different thing from a complete air-conditioning system (First Co fan coil page). A chilled-water version needs a water plant, while a refrigerant-based indoor unit needs its matched refrigeration equipment (First Co fan coil page).

Does a fan coil provide fresh air?

Do not assume it does. Moving room air through a coil is not the same as bringing in outdoor ventilation air, so the building design must set out how ventilation is provided and how its load is covered (First Co fan coil page).

Can a fan coil provide both heating and cooling?

Yes, First Co says, if the chosen configuration and the system it connects to both support it (First Co fan coil page). Look up the model's own documents for whether it has a heating coil, electric heat or a heat-pump setup (First Co fan coil page).

Which fan coil is best for an apartment?

First Co ties the choice to the building's system, its loads, the space on hand and how the unit gets serviced (First Co fan coil page). Start with the product category, then compare the specific models with the equipment schedule (First Co fan coil page).

Do I need to call a pro for this?

Yes. The manual says installation "should be performed only by a licensed contractor" (FWA-HW manual), and refrigerant, electrical, gas, combustion and venting work also belongs to a licensed contractor. Checking or changing the air filter is the homeowner check that fits here.

Related

Questions about a specific system can go to Blume Mechanical Service at (727) 330-9131.

Sources: First Co., What Is a Fan Coil Unit? Fan Coil vs Air Handler (blog, November 18, 2026), https://www.firstco.com/blog/posts/what-is-a-fan-coil-unit/ · First Co., Installation, Operation & Maintenance, FWA-HW Series Fan Coil Units, IOM 6701 Rev B 07/25, https://firstco.com/wp-content/uploads/2022/11/IOM6701.pdf