Generator run time, fuel burn and oil care in a long outage

For extended operation, Kohler says to check the oil level at the interval for the model, which is every 8 hours on its 14 and 20 kW units and every 24 hours on its 26 kW units (Kohler). Kohler calls for stopping the engine and letting it sit for several minutes before checking the oil level (Kohler).

Tampa Electric reported nearly 600,000 outages on its system after Hurricane Milton (Tampa Electric). In September 2022, Hurricane Ian cut power to more than 2.6 million Florida customers, with some losing service for more than two weeks (EIA). Kohler calls for more frequent service when its standby units run for long hours or operate in extreme weather or dusty or dirty conditions (Kohler).

Fuel burn at different electrical loads

Kohler rates the 60 Hz 14RCA and 14RCAL at 124 cubic feet of natural gas per hour at half load and 193 at full load (Kohler). On propane, Kohler gives 60 cubic feet per hour at half load and 81 at full load for those models (Kohler). For the 60 Hz 20RCA and 20RCAL, Kohler lists 161 cubic feet per hour on natural gas at half load and 281 at full load, with propane rates of 82 and 136 cubic feet per hour at those same loads (Kohler). For the 60 Hz 26RCA and 26RCAL, Kohler gives 180 cubic feet per hour of natural gas at half load and 290 at full load (Kohler). At those loads the propane figures are 85 and 129 cubic feet per hour, respectively (Kohler).

Propane in the tank and propane the tank can deliver

PERC says propane containers are typically filled to four-fifths of capacity so the liquid has space to expand when it warms (PERC). PERC estimates how fast an aboveground ASME tank can supply propane vapor using the tank dimensions, liquid level and temperature (PERC). For a half-full 250-gallon tank, PERC gives a maximum intermittent draw without frosting of 288,100 Btu per hour when the lowest 24-hour average outdoor temperature reaches 40 degrees Fahrenheit, under the table's humidity assumption (PERC). For a half-full 500-gallon tank under those same conditions, PERC gives 478,800 Btu per hour (PERC). For a continuous draw, PERC says to use one-quarter of the intermittent rate (PERC).

Oil checks and changes on Kohler standby units

Kohler calls for an oil-level check before each use and at the model's scheduled intervals during extended operation (Kohler). The engine must be stopped for the check (Kohler). Kohler uses the operating hours shown on the generator controller to schedule service, alongside calendar intervals such as yearly service (Kohler). Kohler schedules the 14 kW models for fresh oil yearly or at 100 operating hours, with a separate oil filter interval of yearly or 200 operating hours (Kohler). Kohler schedules standard oil changes on the 20 and 26 kW models yearly or at 150 operating hours, with a new filter each time the oil is changed (Kohler). Kohler also offers a premium 10W-50 extended-life synthetic oil for the 26 kW models, with a change interval of 2 years or 300 operating hours (Kohler). Kohler says its standby equipment must be serviced by qualified electrical personnel (Kohler).

When utility power returns

In Kohler's automatic standby setup, the transfer switch detects a utility outage, signals the generator to start and then connects it to the electrical load (Kohler). Once utility service returns, the switch puts the load back on utility power first (Kohler). The Kohler generator then runs unloaded to cool the engine before shutting down (Kohler).

Carbon monoxide and backfeeding

A portable generator must never run indoors, in a garage, or in any other enclosed or partially enclosed space, even with ventilation (Washington State Department of Health). Fans and open windows or doors cannot keep carbon monoxide from building up in the home (Washington State Department of Health). Portable generators belong outdoors at least 20 feet from buildings and away from vents, doors and windows that could admit exhaust (Washington State Department of Health). Air currents can still carry carbon monoxide into the home at that distance, so a working indoor carbon monoxide alarm is important (Washington State Department of Health). A generator must never feed house wiring through a wall outlet because backfeeding can electrocute utility workers or neighbors on the same transformer (Washington State Department of Health). Connecting generator power to household wiring requires a transfer switch installed by a qualified electrician (Washington State Department of Health).

Frequently asked

Does a low oil pressure shutdown replace an oil check?

Kohler says its low oil pressure shutdown cannot protect against damage from a low oil level (Kohler). On the 26RCA and 26RCAL, Kohler uses a separate level sensor that stops the engine or prevents it from starting if the oil drops below a set level (Kohler).

How much gas does a 20RCA use at a quarter load?

Kohler puts the 60 Hz 20RCA at 127 cubic feet per hour on natural gas at quarter load (Kohler). At the same load on propane, Kohler gives 59 cubic feet per hour (Kohler).

What oil does Kohler specify?

Kohler recommends synthetic 5W-30 or 10W-30 meeting API service class SG, SH or SJ (Kohler). For the 26 kW model, Kohler also offers its extended-life synthetic oil in 10W-50 (Kohler).

Do I need to call a pro for this?

Yes. The work belongs to a licensed contractor. Kohler requires qualified electrical personnel for installation and service of its standby equipment (Kohler). A qualified electrician must install the transfer switch when connecting a generator to household wiring (Washington State Department of Health).

Related

Need a generator supplied? Blume can supply a generator; the electrical installation is referred to a licensed electrician. Blume Mechanical Service, license CAC-1822618, serves Pinellas, Hillsborough and Pasco counties.

Sources: Kohler, 14RCA/14RCAL Specification Sheet G4-270, https://resources.kohler.com/power/kohler/residential/pdf/g4270.pdf · Kohler, 20RCA/20RCAL Specification Sheet G4-272, https://resources.kohler.com/power/kohler/residential/pdf/g4272.pdf · Kohler, 26RCA/26RCAL Specification Sheet G4-315, https://resources.kohler.com/power/kohler/residential/pdf/g4315.pdf · Kohler, Operation Residential/Commercial Generator Sets Models 14RCA 14RCAL 20RCA 20RCAL 26RCA 26RCAL TP-7092, https://resources.kohler.com/power/kohler/residential/pdf/tp7092.pdf · PERC, Dispensing Propane Safely into Agricultural Equipment, https://cloudinary.propane.com/images/v1600343616/website-media/Dispensing_Propane_Safely_Ag_Equip/Dispensing_Propane_Safely_Ag_Equip.pdf · PERC, The Propane Technical Pocket Guide: Data and Guidance for Residential and Commercial, https://cloudinary.propane.com/image/upload/v1664396780/Residential:Commercial/Brochures/4482-BR-21_Technical-Pocket-Guide_v3_HRpg.pdf · EIA, U.S. electricity customers averaged five and one-half hours of power interruptions in 2022, https://www.eia.gov/todayinenergy/detail.php?id=61303 · Tampa Electric, Achieving Power Restoration Milestones After Hurricane Milton, https://www.tampaelectric.com/mediacenter/2024/Tampa-Electric-Achieving-Power-Restoration-Milestones-After-Hurricane-Milton/ · Washington State Department of Health, Generator Use During a Power Outage, https://doh.wa.gov/emergencies/be-prepared-be-safe/severe-weather-and-natural-disasters/power-outages/generator-use-during-power-outage