Duct Register Boot: What It Is and Why Sealing Matters

A register boot is the connection between a supply duct and a supply register (FSEC CR-397-91). FSEC CR-397-91 calls it the supply box (boot), and says the connection frequently leaks, with the box typically slipped over the register flanges and no seal applied (FSEC CR-397-91). In the FSEC blower door tests, ACH50 fell from 12.7 to 11.1 when the supply and return registers were covered with paper and tape (FSEC CR-397-91).

FSEC CR-397-91 is a study of 160 central Florida homes, and its supply leak ranking covers site-built homes (FSEC CR-397-91). Its findings describe the boot as a leak site. The study found large leaks in the air distribution system, and the report reads the change in blower door results as holes in that system (FSEC CR-397-91).

What the boot is and where it sits

A register boot is the connection between a supply duct and a supply register, and the box is typically slipped over the register flanges (FSEC CR-397-91). FSEC CR-397-91 calls it the supply box (boot), and says that typically no seal is applied at that joint (FSEC CR-397-91). FSEC CR-1789-06 also describes a branch duct connecting to the supply boot (FSEC CR-1789-06). The source also uses box for a return plenum, which is the central return where return ductwork reaches the house floor (FSEC CR-397-91). The same study's smoke test checked each supply and return register with the air handler off, and the report says that if smoke moved quickly into a register, leakage existed in the nearby ducts (FSEC CR-397-91).

Why sealing the boot matters

FSEC CR-397-91 links sealing to whole-house leakage. Tracer gas testing on 160 central Florida homes found 0.91 air changes per hour of infiltration with the air handler running, against 0.28 with it off (FSEC CR-397-91). The blower door section, covering 100 homes, shows ACH50 at 12.7 falling to 11.1 once the supply and return registers were covered with paper and tape (FSEC CR-397-91). The abstract reports the same 12.7 and 11.1 values for 99 homes (FSEC CR-397-91). The report reads that drop as holes in the air distribution system (FSEC CR-397-91). FSEC CR-1789-06 describes a pressure pan test with the air handler off: the pan is set on each supply register and return grill in turn, and a reading of 50 pascals, the maximum, would mean a duct is completely disconnected (FSEC CR-1789-06). The average pressure pan reading in that study was 0.64 pascals, which the report calls slight to moderate duct leakage on average (FSEC CR-1789-06).

How the supply boot ranks among leaks

FSEC CR-397-91 ranks supply leaks in site-built homes by visual inspection, and places the supply box second, after supply plenums (FSEC CR-397-91). The source describes these leaks as very common, and commonly small to moderate in size, with large leaks in a small share of homes (FSEC CR-397-91). Its summary places supply box to register connections third of four, behind the plenum-to-air-handler junction and supply duct connections (FSEC CR-397-91). FSEC CR-1789-06 says typical operating pressures might be about +5 pascals at supply boots and -140 at the air handler (FSEC CR-1789-06). It says the amount of leakage depends on where the leaks are and the pressure at each location (FSEC CR-1789-06). Leakage mainly at the air handler, where typical operating pressure might be -140 pascals, may be five times greater than leakage mainly at a branch duct connection to a supply boot (FSEC CR-1789-06). In the 39 houses where that pressure pan testing was done, the report counts 524 supply registers: 147 read 0.0 to 0.2 pascal, 279 read 0.3 to 1.0 pascal, 76 read 1.1 to 2.0 pascals, 17 read 2.1 to 4.0 pascals and 5 read 4.1 pascals or higher (FSEC CR-1789-06). It reads the first group as essentially no significant leakage, and the 1.1 to 2.0 group as significant leakage (FSEC CR-1789-06).

Sealing methods and a combustion safety check

DOE Building America B21 says prior research supports the value of sealing ducts in unconditioned spaces (DOE Building America B21). B21 lists sealing the furnace, the air handler and all ductwork so they are airtight among its current practices for new construction or retrofits (DOE Building America B21). B21 says "Furnace or air handler and all ducts should be sealed with mastic or UL 181A or 181B tape" (DOE Building America B21). After sealing, B21 directs a combustion safety test aimed at backdrafting of gas (DOE Building America B21).

Frequently asked

Where is a register boot located?

It sits where the supply duct meets the supply register, and the box is typically slipped over the register's flanges (FSEC CR-397-91).

Why do supply boots leak?

FSEC CR-397-91 says the connection frequently leaks, and the box is typically placed over the register flanges with no seal applied (FSEC CR-397-91).

Does sealing the registers change measured leakage?

Measured ACH50 fell from 12.7 to 11.1 in the FSEC CR-397-91 blower door tests after the registers were covered with paper and tape (FSEC CR-397-91).

How large are boot leaks?

FSEC CR-397-91 says these leaks are very common, and commonly small to moderate in size (FSEC CR-397-91).

How are leaks at the registers found?

FSEC CR-397-91 pressurized the house to about 15 Pa and used a smoke stick on each supply and return register with the air handler off. If smoke raced into a register, the report says leakage existed in nearby ducts (FSEC CR-397-91).

Do I need to call a pro for this?

Maybe. The homeowner checks here are the air filter, the thermostat settings, and clearing things away from vents, returns and the outdoor unit. Sealing the boot connection is outside those checks, and the combustion safety test after sealing is combustion work, so it goes to a licensed contractor (DOE Building America B21).

Related

Questions about a specific system can go to Blume Mechanical Service at (727) 330-9131.

Sources: FSEC, FSEC-CR-397-91 (Florida Solar Energy Center air distribution leakage study), https://www.fsec.ucf.edu/en/publications/pdf/FSEC-CR-397-91.pdf · FSEC, FSEC-CR-1789-06 (Florida Solar Energy Center combustion and duct study), https://www.fsec.ucf.edu/en/publications/pdf/FSEC-CR-1789-06.pdf · DOE Building America, Duct Systems (B21), https://www1.eere.energy.gov/buildings/publications/pdfs/building_america/ns/b21_duct_systems.pdf