HVAC, explained
EPA leak repair rules for commercial cooling systems
EPA says owners must take corrective action when an appliance with a full charge of 50 or more pounds leaks ozone-depleting refrigerant above the trigger rate (EPA). For commercial refrigeration, the trigger rate is 20 percent, and for comfort cooling it is 10 percent, over a 12-month period (EPA). Owners must repair the leak within 30 days from the date it was discovered, or develop a retrofit or retirement plan (EPA).
Large commercial refrigeration and comfort cooling systems carry enough refrigerant that federal leak repair rules apply to them. This page explains which equipment the rules cover, how the trigger rates work, the deadlines for repair, the verification tests, and the steps technicians follow when a leak blocks normal service. Each statement names its source.
Which equipment the rule covers
Owners must take corrective action when an appliance with a full charge of 50 or more pounds is discovered to be leaking ozone-depleting refrigerant above the trigger rate (EPA). Comfort cooling means air-conditioning appliances used to control heat or humidity in occupied facilities (EPA).
Chillers and commercial split systems are listed as comfort cooling appliances (EPA). Commercial refrigeration means refrigeration appliances used in the retail food and cold storage warehouse sectors (EPA).
Retail food refrigeration includes equipment in supermarkets, convenience stores and restaurants (EPA). Cold storage includes refrigeration equipment used to store meat, produce, dairy products and other perishable goods (EPA). EPA's comfort cooling definition covers residential, office and commercial buildings (EPA).
Trigger rates
EPA's trigger leak rates apply over a 12-month period (EPA). EPA's trigger rates are 20 percent for commercial refrigeration and 10 percent for comfort cooling and all other appliances (EPA).
Confirm the current trigger rates with EPA before you rely on them (EPA). The 20 percent and 10 percent figures are the values EPA lists for each appliance type (EPA).
Repair or plan within 30 days
Owners must repair leaks within 30 days from the date the leak was discovered (EPA). The other route is a retrofit or retirement plan, which must be developed within 30 days and completed within 1 year (EPA).
A copy of the retrofit or retirement plan must be kept on site (EPA). The original plan must be made available to EPA upon request (EPA).
Verification tests after a repair
Owners of appliances that exceed the trigger rate must conduct initial and follow-up verification tests at the conclusion of any repair efforts (EPA). EPA says these tests are essential to ensure that repairs have been successful (EPA).
An appliance that needs more time may be subject to recordkeeping and reporting requirements (EPA). EPA ties the verification tests to repairs on appliances that exceed the trigger rate (EPA).
Extra time for industrial process shutdowns
In cases where an industrial process shutdown is required, a repair period of 120 days is substituted for the normal 30-day repair period (EPA). This longer period applies to industrial process shutdowns only, and not to commercial refrigeration or comfort cooling (EPA).
Otherwise, the normal 30-day repair period applies (EPA). The 120-day period is a substitute for the 30-day period in those cases only (EPA).
Mothballed and idle systems
For all appliances subject to the leak repair requirements, the timelines may be suspended if the appliance has been mothballed (EPA). Mothballing means to evacuate refrigerant from an appliance to at least atmospheric pressure and to temporarily shut down that appliance (EPA).
However, the timelines pick up again as soon as the system is brought back on-line (EPA). Mothballing requires evacuating refrigerant to at least atmospheric pressure, as EPA defines the term (EPA).
Evacuation when a leak blocks service
If technicians cannot evacuate to the specified levels because of refrigerant leaks, they must follow EPA's listed steps (EPA). Technicians must isolate leaking components from non-leaking components wherever possible (EPA). They must evacuate non-leaking components to the specified levels (EPA).
A repair that is not major and is not followed by evacuation must meet EPA's listed requirements (EPA). EPA's listed steps apply when leaks keep technicians from reaching the specified levels (EPA).
What EPA says about leaks in general
EPA's homeowner guidance says technicians should locate and repair leaks instead of topping off a leaking system (EPA). Major leaks rarely develop in properly installed and regularly maintained units (EPA).
The homeowner page is written for residential air conditioners (EPA). EPA's homeowner guidance says major leaks rarely develop in properly installed and regularly maintained units (EPA).
Frequently asked
Which appliances does the leak repair rule cover?
Owners must take corrective action when an appliance with a full charge of 50 or more pounds leaks above the trigger rate (EPA). Chillers and commercial split systems are listed as comfort cooling appliances (EPA).
How long do I have to fix a leak?
Owners must repair leaks within 30 days from the date the leak was discovered (EPA). The other route is a retrofit or retirement plan, which must be completed within 1 year (EPA).
What is a trigger rate?
EPA's trigger leak rates apply over a 12-month period (EPA). The trigger rate is 20 percent for commercial refrigeration and 10 percent for comfort cooling and all other appliances (EPA).
Do I need a verification test after a repair?
Owners of appliances that exceed the trigger rate must conduct initial and follow-up verification tests at the conclusion of any repair efforts (EPA). EPA says these tests are essential to ensure that repairs have been successful (EPA).
Can the leak repair timeline be paused?
The timelines may be suspended if the appliance has been mothballed (EPA). The timelines pick up again as soon as the system is brought back on-line (EPA).
What if a leak stops a technician from evacuating the system?
If technicians cannot evacuate to the specified levels because of refrigerant leaks, they must follow EPA's listed steps (EPA). Technicians must evacuate non-leaking components to the specified levels (EPA).
Related
- Refrigerant recovery, recycling and reclaim explained
- Global warming potential (GWP) for refrigerants explained
- EPA 608 Certification and the Refrigerant Rules Homeowners Should Know
Running a commercial refrigeration or comfort cooling system? Blume Mechanical Service (license CAC-1822618) repairs, installs and maintains HVAC and refrigeration equipment in Pinellas, Hillsborough and Pasco counties. Call 727-330-9131.
Sources: U.S. Environmental Protection Agency (EPA) — Stationary Refrigeration Leak Repair Requirements (https://www.epa.gov/section608/stationary-refrigeration-leak-repair-requirements) · U.S. Environmental Protection Agency (EPA) — Stationary Refrigeration Service Practice Requirements (https://www.epa.gov/section608/stationary-refrigeration-service-practice-requirements) · U.S. Environmental Protection Agency (EPA) — Homeowners and Consumers: Frequently Asked Questions (https://www.epa.gov/ods-phaseout/homeowners-and-consumers-frequently-asked-questions)